Get free alertsFree alerts

How to win fire alarm, fire door and security maintenance contracts

Last reviewed 28 October 2026. General guidance, not legal advice.

On this page (10 parts)
  1. Why public buyers keep buying this work
  2. What gets serviced, and how often
  3. Who buys, and how they buy
  4. The certification buyers ask for
  5. Intruder alarms and police response
  6. CCTV and access control: the extra checks
  7. What a strong bid shows
  8. Practical steps
  9. Frequently asked questions
  10. Sources

This guide is for owners of small fire protection and security firms who want maintenance contracts from councils, housing associations, the NHS, schools and universities. It covers the law behind the work, servicing intervals, the certification buyers ask for, police response, CCTV rules and what a strong bid shows.

Key points

Why public buyers keep buying this work

The Regulatory Reform (Fire Safety) Order 2005 (the Fire Safety Order) applies in England and Wales. Article 17 says that, where needed to keep people safe, the responsible person must ensure premises, facilities, equipment and devices are "subject to a suitable system of maintenance" and kept "in efficient working order and in good repair". Scotland and Northern Ireland have their own fire safety rules.

Since 1 October 2023, changes made by section 156 of the Building Safety Act 2022 mean every responsible person must record the full fire risk assessment and their fire safety arrangements. Anyone appointed to help with it must be competent, and their name must be recorded.

In England, the Fire Safety (England) Regulations 2022 came into force on 23 January 2023. They added two duties that create regular work in blocks of flats:

The same height test (at least 18 metres or 7 storeys, with at least 2 residential units) defines a higher-risk building under the Building Safety Act 2022. Our housing association guide explains what that means for landlords.

What gets serviced, and how often

System Routine checks and servicing Where it comes from
Fire alarms Weekly test by the site using a different call point each week; service about every 6 months (5 to 7 months acceptable) Government small premises guide; BS 5839-1:2025
Emergency lighting Monthly functional test; annual inspection and test by a competent contractor Government small premises guide; BS 5266-1
Extinguishers Monthly visual check by the site; basic service every 12 months; extended service every 5 years for water and powder; overhaul every 10 years for CO2 BS 5306-3, as summarised by BAFE
Fire doors (flats over 11 m) Communal doors every 3 months; flat entrance doors every 12 months Fire Safety (England) Regulations 2022
Firefighting equipment (flats 18 m or 7 storeys and over) Monthly checks, on top of normal maintenance Fire Safety (England) Regulations 2022

BS 5839-1:2025 also adds a clause on remote services and cyber security. The 2025 revision of BS 5266-1 says photometric performance should be verified at least every five years.

For intruder alarms, CCTV and access control, the contract and the system's standards usually set the servicing.

Who buys, and how they buy

Recent examples:

Lots like these give a small extinguisher or alarm firm a realistic way in. Our guide to frameworks, DPS and dynamic markets explains how to get on these lists.

The certification buyers ask for

Work Schemes buyers may ask for
Fire alarms BAFE SP203-1 (covers design, installation, commissioning and maintenance)
Emergency lighting BAFE SP203-4
Extinguishers BAFE SP101
Dry and wet risers BAFE SP105
Fire risk assessment BAFE SP205 for companies; individual registers such as the IFE Fire Risk Assessors Register
Fire doors FDIS for inspectors; BM TRADA Q-Mark fire door maintenance and installation; IFC Certification installer schemes
Passive and active fire protection installers FIRAS (Warringtonfire)
Sprinklers LPCB LPS 1048
Intruder alarms, CCTV, access control NSI Gold or Silver; SSAIB

Most buyers will also want health and safety accreditation. See SSIP and CHAS.

Intruder alarms and police response

The NPCC policy is called Police Operational Advice and Security Industry Requirements for Response to Security Systems, most recently updated in May 2025. A police force gives each qualifying system a URN, which flags the premises for police response when a verified alarm signal comes in.

NSI says a system must be installed, maintained and monitored by NSI approved companies to be eligible, and SSAIB says its certification supports URN applications. Police can withdraw response when false alarms reach an unacceptable level: West Yorkshire Police gives three false calls in a rolling 12 months as an example. So show buyers how you keep false alarms down.

CCTV and access control: the extra checks

What a strong bid shows

Practical steps

  1. List the systems you already service and match each to a scheme in the table above.
  2. Get third-party certification for your main service line before you bid on larger contracts.
  3. Register on the central digital platform and local buyers' supplier portals.
  4. Watch for framework renewals and preliminary market engagement notices, and respond to them.
  5. Target lots that match your trade, such as extinguishers or fire door inspection, instead of whole-building packages.
  6. Offer to subcontract to larger FM firms holding public contracts. See subcontracting on public contracts.

BidTrowel lists open fire and security contracts at /tenders/fire-security/ and can email you new ones.

Frequently asked questions

Do I need BAFE to service fire alarms for a council?

Not by law. But many buyers ask for BAFE or an equivalent, and without one you may fail a pass or fail question.

Who can do the quarterly fire door checks in flats?

Government guidance says the basic regulation 10 checks do not need a specialist, so trained caretakers or maintenance staff can do them. Repairs and replacements must be done by a competent person, which is where specialist firms come in.

How often should a fire alarm be serviced?

BS 5839-1:2025 says about every 6 months, with any visit between 5 and 7 months after the last one acceptable. The site should also test the alarm weekly.

Can I win security contracts without NSI or SSAIB?

Yes, where the buyer does not ask for it. But for alarms with police response, NSI and SSAIB both link their certification to URN eligibility.

This guide is general information, not legal advice.

Sources

Get public contracts that fit your firm by email. Free: every weekday for your first two weeks, then Mondays when there are new matches.

Get free alerts